Tags: Precise-Log comunications

How to Use Access Point (AP) of Data Logger

How to Use Access Point (AP) of Data Logger

MEI 03/06/2019 0
Recently, PRECISE-LOG data loggers were upgraded with a new communication feature called 'AccessPoint Server' mode. In this mode, the data logger will provide an Access Point for host computer to join in order to make a quick and easy point-to-point communication.To use this new feature, please download the new version of SiteView software (version 4.1.3) and upgrade PRECISE-LOG with new firmware version 2.04.The followings are the detailed steps to communicate with PRECISE-LOG data logger through 'AccessPoint Server' mode:Click on 'Configure' button on the logger's status toolbar:Click 'WIFI Settings' tab and choose 'AccessPoint Server' mode:Note that the 'AP SSID' is read only and your host PC needs to connect to this access point. The login password is the one you set below 'AP SSID' field.The logger's IP address is fixed to '10.10.100.254'Change 'AP Password' as needed. Minimum length:8 characters.Click 'Save WIFI settings' button.This will save the settings to the logger. Please wait a minute for the logger to establish its WIFI access point (AP).From the host computer, open the WIFI network list to look for an access point named 'PL' + 'Serial Number of the logger'Click the a...